COOLING
EQUIPMENT SELECTION
Consider
System A (Table 7-4) with 80°F return air :
¾
At low fan speed, System
A provides 35,800
Btu/hour, 0.71 SHF, and thus 29% latent
cooling (dehumidification).
¾
At high fan speed, System
A provides 38,800
Btu/hour, but a 0.81 SHF, and only 19% latent cooling. This is not enough dehumidification in many Kentucky
homes.
Table 7-4
Sample Cooling System A Data,
|
||||
Total
Air Volume (cfm)
|
Total
Cooling Capacity (Btu/h)
|
Sensible
Heating Fraction (SHF)
|
||
Dry Bulb
(°F)
|
||||
75°F
|
80°F
|
85°F
|
||
950
|
35,800
|
0.58
|
0.71
|
0.84
|
1,200
|
37,500
|
0.61
|
0.76
|
0.91
|
1,450
|
38,800
|
0.64
|
0.81
|
0.96
|
Consider
System B (Table 7-5) with 80°F return air:
¾ At low fan speed,
System B provides
32,000 Btu/ hour, 0.67 SHF and 33% dehumidification.
¾ At high fan speed,
System B provides
35,600 Btu/hour, 0.76 SHF and 24% dehumidification.
Table 7-5
Sample Cooling System B Data
|
||||
Total
Air Volume (cfm)
|
Total
Cooling Capacity (Btu/h)
|
Sensible
Heating Fraction (SHF)
|
||
Dry Bulb
(°F)
|
||||
75°F
|
80°F
|
85°F
|
||
950
|
32,000
|
0.56
|
0.67
|
0.78
|
1,200
|
34,100
|
0.58
|
0.71
|
0.84
|
1,450
|
35,600
|
0.61
|
0.76
|
0.90
|