EVAPORATIVE
COOLING APPLICATIONS
Direct Free Cooling Applications
The condenser of the cooling
unit is cooled by water in systems using cooling towers. The condenser is of
the shell and tube type. The coolant vapour passing outside the pipes is cooled
and condensed by the condenser water circulating within the pipes. In this stage, the cooling of the condenser
water is done by the tower. This is how the condenser water is cooled when the
chiller is operated in high outdoor temperatures. However, as the ambient
temperature falls below the temperature of the cold water used in the cooling
system, the cooling group no longer needs to be used. In this case, in Direct Systems, the chiller is bypassed
and the condenser water from the tower is sent to the system directly as the
cooling water required by the system. The basic advantage of this system in
towers operating as open circuits can be summarised as follows: The required
cold water temperature can be approximated to the wet bulb temperature of the environment.
In this case, the maximum benefit will be gained from Free Cooling. However, a
serious disadvantage of the system is the pollution caused by the relatively
dirty condenser water in the clean cold water system. Even though attempts to
alleviate pollution by methods like filtration, this system has been lately
unpopular among applicators. Cooling tower applications operating as closed
circuit-indirect systems or dry cooler applications catering to the same
demands eliminate this problem.
Indirect Free
Cooling Applications
In Indirect Systems, the
condenser water circuit and cold water circuit are separate. The pollution risk
which is an issue in open circuit systems does not exist in indirect-closed
circuit applications. However, annexing an additional heat transfer surface to
the system leads to a higher water temperature as compared to open circuit
water cooling towers. This cause the efficiency of Free Cooling to somewhat
drop.
Indirect systems can be
applied in three main ways:
1.Systems
utilizing closed circuit cooling towers:
The use of Closed Circuit
Cooling Towers is common in Free Cooling. As mentioned above, it eliminates the
risks of pollution, etc. seen in open circuit systems. In the summer season
which is the normal operating period of the cooling group, the condenser water
coming from the tower circulates from the condenser within a closed circuit. In
winter months however, when only Free Cooling is used, the water coming from
the tower circulates in the cold water circuit within the closed circuit.
Figure 2.b shows the Load
Sharing Closed Circuit Cooling Towers Free Cooling application. In this system,
the returned cooling water undergoes a pre-cooling process prior to entering
the evaporator. This application decreases the cooling load on the chiller.
This application increases system efficiency in interim seasons.
In water cooling towers,
depending on design, water can be cooled to a temperature up to 3-6ºC above wet
bulb temperature. In closed circuit cooling towers, the water temperature which
can be attained is up to above 2-3ºC the temperature that can be achieved with
open circuit water towers. In ideal conditions wet bulb temperature can be
approached closely by increasing tower dimensions; however in this case the
cost of investment will increase dramatically. While water cooling towers are
advantageous in terms of initial investment cost, they can lead to problems in
operation. In case the water from the water tower is used directly, this causes
calcification and pollution of cooling exchangers. Furthermore, the portion of
the water used in water towers which is lost to evaporation needs to be constantly replenished. Additionally,
the water needs to be flushed periodically in order to get rid of sedimentation
within the tower tank; the water in the tank may reach extremely high degrees
of hardness and pollution dues to the accumulation of scale and other similar
substances in water diminished by evaporation in the system. The use of these
systems should also be evaluated in terms of water loss and water quality.
2.Systems Utilizing Supplemental Heat
Exchangers:
These are applications
utilizing a separate heat exchanger within the system. The heat exchangers used
in these cases are usually plate type ones. In the winter season, the heat load
in the cold water circuit is received by the tower water through a supplemental
heat exchanger without the need for a chiller.
3.Refrigerant Gas
circulation system:
The Refrigerant Gas
circulation system is one which is rarely used. In cases where the condenser
water can be obtained below the desired cold water temperature, the chiller
operates like a thermosyphon. The low temperature condenser water condenses the
gaseous refrigerant fluid within the condenser. The condensed refrigerant fluid
is transferred to the evaporator by the aid of gravity or an auxiliary pump.
The high temperature cooling water circulating in the system causes the
refrigerant fluid within the evaporator to vaporise. The differential pressure
between the Evaporator and the Condenser causes the gas to return to the
Condenser. In this system, the flow between the evaporator and the condenser is
facilitated through by-pass connections. This system renders the operation of a
compressor unnecessary. This system is not applicable to all cooling groups.
And in groups where it is applied, the Free Cooling capacity is limited to
10-30% of the design capacity of the chiller. The Free Cooling capacity depends
on the design specifications of the chiller and the temperature difference
between the desired water temperature and the condenser water temperature.
www.bilkargroup.com
www.bilkarsogutma.com.tr
info@bilkargroup.com
+90 212 343 50 40
+90 553 343 50 40

Hiç yorum yok:
Yorum Gönder