HVAC SYSTEM
For proper operation, a HVAC system must be properly
designed, sized and installed. A proper HVAC system will provide an improved
indoor environment and minimize the cost of operation. In the planning process
for an energy efficient home, everything should be done to reduce the heating
and cooling load on the home before the HVAC system is designed.
SIZING
When considering a HVAC system for a residence, remember
that energy efficient and passive solar homes have less demand for heating and
cooling. Substantial savings may be obtained by installing smaller units that
are properly sized to meet the load. Because energy bills in more efficient
homes are lower, higher efficiency systems will not provide as much annual
savings on energy bills and may not be as cost effective as in less efficient
homes.
Not only does oversized equipment cost more, but also it
can waste energy. Oversized equipment may also decrease comfort. For example,
an oversized air conditioner cools a house but may not provide adequate
dehumidification. This cool, but clammy air creates an uncomfortable
environment.
Many contractors select air conditioning systems based on
a rule, such as 600 square feet of cooled area per ton of air conditioning (a
ton provides 12,000 Btu per hour of cooling). Instead, use a sizing procedure
such as
·
Calculations
in Manual J published by the Air Conditioning Contractors Association;
·
Similar procedures developed by the American Society
of Heating, Refrigeration, and Air Conditioning
Engineers (ASHRAE); or
·
Software procedures developed by electric
or gas utilities, the U.S. Department of Energy or HVAC equipment manufacturers.
The heating and
cooling load calculations rely on the
outside winter and summer
design temperatures (see the appendix for a definition)
and the size and type of construction for each component of the building
envelope, as well as the heat given off by the lights, people, and equipment
inside the house. If a zoned heating and cooling system is used, the loads in
each zone should be calculated. Table 7-3 compares the size of heating and
cooling systems for the homes in Table 2-2. The more efficient home reduces the
heating load 35% and the cooling load 26%. Thus, the $600 to $1,000
savings from reducing
the size of the
HVAC equipment offset the additional cost of the energy features
in the more efficient home.
Table 7-3
Equipment Sizing Comparison
|
|||
Type of House
|
Code Home HERS=98
|
ENERGY STAR®
Home HERS=85
|
Exceeds ENERGY
STAR® Home
HERS=70
|
HVAC System Sizing
|
|||
Heating (BTU/hour)
|
52,200
|
38,800
|
25,700
|
Cooling (BTU/hour)
|
31,700
|
25,700
|
19,800
|
Estimated tons of cooling*
|
3.0
|
2.5
|
2.0
|
Square feet/ton
|
667
|
800
|
1,000
|
*Estimated at
110% of calculated size. There are 12,000 Btu/hour in a ton of cooling.
|
|||
Oversimplified rules-of-thumb would have provided an
oversized heating and cooling system for the more efficient home. The typical
rule-of-thumb in Kentucky has been to allow for 600 square feet per ton of air
conditioning. Since the home has 2,000 square feet of conditioned space, HVAC
contractors could well provide 3.5 to 4 tons of cooling (2,000 ÷ 600 = 3.33,
then round up.) The oversized unit would have cost more to install. In
addition, the operating costs would be higher. The oversized unit would suffer
greater wear and may not provide adequate dehumidification.
Proper sizing includes designing the cooling system to
provide adequate dehumidification. In a mixed- humid climate, it is important
to calculate the latent load. The latent load is the amount of dehumidification
needed for the home. If the latent load is ignored, the home may become
uncomfortable due to excess humidity.
The Sensible Heating Fraction (SHF) designates the portion
of the cooling load for reducing indoor temperatures (sensible cooling). For
example, in a HVAC unit with a 0.75 SHF, 75% of the energy expended by the unit
goes to cool the temperature of indoor air. The remaining 25% goes for latent
heat removal—taking moisture out of the air in the home. To accurately estimate
the cooling load, the designer of a HVAC system must also calculate the desired
SHF and thus, the latent load.
Many homes in Climate
Zone 4 have design SHFs of approximately 0.7. This means that 70% of the
cooling will be sensible and 30% latent. Systems that deliver less than 30%
latent cooling may fail to provide adequate dehumidification in summer. It
takes 15 minutes for most air conditioners to reach peak efficiency. During
extreme outside temperatures (under 32°F in winter and over 88°F in summer),
the system should run about 80% of the time. Oversized systems cool the home
quickly and often never reach their peak operating efficiency.
www.bilkargroup.com
www.bilkarsogutma.com.tr
info@bilkargroup.com
+90 212 343 50 40
+90 553 343 50 40
Hiç yorum yok:
Yorum Gönder